A unique earth ground tester that performs testing with and without stakes. Tests 3- and 4-pole fall-of-potential, and 4-pole soil resistivity (with stakes). Performs selective earth ground rod testing (one clamp + stakes). Performs stakeless earth ground rod testing (two clamps). Features Automatic Frequency Control (AFC) to minimize the effect of interference.

SKU: FLUKE 1625-2
Stock status: Out of stock
Contact us for pricing and availability.
Description

Key features

  • A unique earth ground tester that performs testing with and without stakes
  • Tests 3- and 4-pole fall-of-potential, and 4-pole soil resistivity (with stakes)
  • Performs selective earth ground rod testing (one clamp + stakes)
  • Performs stakeless earth ground rod testing (two clamps)
  • Features Automatic Frequency Control (AFC) to minimize the effect of interference

Get fast, accurate earth ground testing using all four test methods

The Fluke 1625-2 earth ground tester measures earth ground loop resistances using only clamps, only stakes, or one clamp and stakes. With the stakeless test method, the Fluke 1625-2 is able to measure earth ground loop resistances for multi-grounded systems using only current clamps. This technique eliminates the dangerous, and time consuming job of disconnecting parallel grounds, and finding suitable locations for auxiliary ground stakes. This allows you to perform earth ground tests in places you’ve not considered before, such as inside buildings, on power pylons, or anywhere you don’t have access to soil.

Keep your options open

If a bonded earth ground system does not exist for the building or structure under test, and there is only one path to ground, you can use the 1625-2 to perform the fall-of-potential test method with stakes.

The 1625-2 Earth Ground Tester offers other advanced features including:

  • Automatic Frequency Control to identify existing interference and choose a measurement frequency to minimize its effect, thus providing a more accurate earth ground value.
  • R* measurement that calculates earth ground impedance at 55 Hz to more accurately reflect the earth ground resistance that a fault-to earth ground would see.

The 1625-2 is also very easy to use. World class accessories speed set up and test time. And the tester tells you which stakes or clamps to connect for each test. The large rotary switch and buttons are easy to operate even with a gloved hand. And you can store up to 1500 records and access them easily via the USB port.

Other useful capabilities:

  • Provides R* measurement that calculates earth ground impedance at 55 Hz to more accurately reflect the earth ground resistance that a fault-to earth ground would see
  • Includes USB port for data storage and transfer
  • Features IP56 rating for outdoor use
  • Offers adjustable limits for quicker testing
  • Comes with a rugged carrying case

What's in the box

  • GEO Earth Ground Tester
  • User's Manual
  • Batteries
  • Quick Reference Guide
  • USB Cable

Manuals + resources


Specifications

  • Memory: Up to 1500 records accessible via USB port
  • Measuring function:
    • Interference voltage and frequency
    • earthing resistance 3- and 4-pole with/without clip-on CT
    • Resistance 2-pole with AC
    • 2- and 4-pole with DC
  • Display: 4 digit (2999 digit) 7 segment LCD, improved visibility
  • Operation: Central rotary switch and function keys
  • Operating temperature: -10 °C to 50 °C
  • Storage temperature: -30 °C to 60 °C
  • Temperature coefficient: ±0.1% of reading per °C, below 18 °C or above 28 °C
  • Type of protection:
    • IP56 for case
    • IP40 for battery door, per EN60529
  • Max voltage, clamp socket: U rms = 0 V (warning)
  • Max voltage between E, ES, S, H: U rms 250 V (misuse)
  • Safety:
    • Double and/or reinforced insulation
    • max 50 V to earth
    • IEC61010-1, Pollution degree 2
  • Quality standard: Developed, designed and manufactured to comply with DIN ISO 9001
  • External field influence: Complies with DIN 43780 (8/76)
  • Auxiliary power: 6 x 1.5 V alkaline (IEC LR6 or type AA)
  • Battery life span:
    • Typ. 3,000 measurements (RE + RH ≤ 1 kΩ)
    • typ. 6,000 measurements (RE + RH > 10 kΩ)
  • Case material: Polyester
  • Interference voltage:
    • Full wave rectification
    • measuring range 1 V to 50 V
    • Display range 0.0 V to 50 V
  • Interference voltage resolution: 0.1 V
  • Interference voltage accuracy: ±(5% of rdg + 5 digit)
  • Interference voltage frequency range:
    • DC
    • AC 45 Hz to 400 Hz sine
  • Interference voltage measuring sequence: Approx. 4 measurements/s
  • Internal resistance: Approx. 1.5 MΩ
  • Max. overload: U rms = 250 V
  • Interference frequency:
    • Oscillation period of the interference voltage
    • measuring range 6.0 Hz to 400 Hz
    • Display range 16.0 Hz to 999 Hz
  • Interference frequency resolution: 0.1 Hz to 1 Hz
  • Interference frequency accuracy: ±(1% of rdg + 2 digit)
  • Voltage range for frequency: 1 V to 50 V
  • RE measuring method: Current and voltage measurement with probe as IEC61557-5
  • RE open circuit voltage: 20/48 V AC
  • RE short circuit current: 250 mA AC
  • RE measuring frequency:
    • 94, 105, 111, 128 Hz manual or automatic (AFC)
    • 55 Hz in function R*
  • Noise rejection: 120 dB (16 2/3, 50, 60, 400 Hz)
  • RE max. overload: U rms = 250 V
  • Electrical Measurement Specifications (IEC 1557)
  • Intrinsic error A:
    • Reference conditions
    • Part 5, 6.1
    • routine test
  • Position E1:
    • Reference position ±90°
    • Part 1, 4.2
    • routine test
  • Supply voltage E2:
    • At limits stated by manufacturer
    • Part 1, 4.2, 4.3
    • routine test
  • Temperature E3:
    • 0 °C and 35 °C
    • Part 1, 4.2
    • type test
  • Series interference voltage E4:
    • See 4.2 and 4.3
    • Part 5
    • type test
  • Probe and electrode resistance E5:
    • 0 to 100 x RA but ≤ 50 kΩ
    • Part 5, 4.3
  • System frequency E7:
    • 99% to 101% of nominal frequency
    • Part 5, 4.3
  • System voltage E8:
    • 85% to 110% of nominal voltage
    • Part 5, 4.3
  • Operating error B:
    • B = ±(|A| + 1.15√(E1²+E2²+E3²+E4²+E5²+E6²))
    • Part 5, 4.3
  • RE range: 0.020 Ω to 300 kΩ
  • RE: Display range 0.001 Ω to 299.9 kΩ
  • RE resolution: 0.001 Ω to 100 Ω
  • RE accuracy: ±(2% of rdg + 2 digit)
  • RE: Operating error ±(5% of rdg + 5 digit)
  • RE measuring time:
    • Typical 8 s with fixed frequency
    • 30 s max. with AFC full cycle
  • Additional error, probe and electrode: RH(RS+2000 Ω)/RE x 1.25x10⁻⁶% + 5 digits
  • Measuring error of RH and RS: Typ. 10% of RE+RS+RH
  • Max. probe resistance: ≤ 1 MΩ
  • Max. auxiliary earth electrode resistance: ≤ 1 MΩ
  • Error check:
    • Automatic check against IEC61557-5 limits
    • Error above 30% shows warning symbol: RS or RH too high
  • Resolution 1 mΩ:
    • RH below 300 Ω at 48 V
    • below 250 Ω at 20 V
  • Resolution 10 mΩ:
    • RH below 6 kΩ at 48 V
    • below 2.5 kΩ at 20 V
  • Resolution 100 mΩ:
    • RH below 60 kΩ at 48 V
    • below 25 kΩ at 20 V
  • Resolution 1 Ω:
    • RH below 600 kΩ at 48 V
    • below 250 kΩ at 20 V
  • RE clamp method:
    • Current and voltage measurement with probe per EN61557-5
    • Branch current measured with additional current transformer
  • RE clamp open circuit voltage: 20/48 V AC
  • RE clamp short circuit current: 250 mA AC
  • RE clamp measuring frequency:
    • 94, 105, 111, 128 Hz manual or automatic (AFC)
    • 55 Hz (R*)
  • RE clamp max. overload: Max U rms 250 V (measurement will not be started)
  • RE clamp range: 0.020 Ω to 300 kΩ
  • RE clamp: Display range 0.001 Ω to 29.99 kΩ
  • RE clamp resolution: 0.001 Ω to 10 Ω
  • RE clamp accuracy: ±(7% of rdg + 2 digit)
  • RE clamp: Operating error ±(10% of rdg + 5 digit)
  • RE clamp additional error: RH(RS+2000 Ω)/RE total x 1.25x10⁻⁶% + 5 digits
  • RE clamp error of RH and RS: Typ. 10% of RE total+RS+RH
  • RE clamp measuring time:
    • Typ. 8 s with fixed frequency
    • 30 s max. with AFC
  • Minimal branch current:
    • 0.5 mA with 1000:1 transformer
    • 0.1 mA with 200:1 transformer
  • Max. interference current through transformer: 3 A with 1000:1 transformer
  • RE clamp conditions: With recommended current clamps/transformers
  • R~ method:
    • Current and voltage measurement
    • 20 V AC square pulse
    • short circuit current above 250 mA AC
  • R~ measuring frequency: 94, 105, 111, 128 Hz manual or automatic (AFC)
  • R~ range: 0.020 Ω to 300 kΩ
  • R~: Display range 0.001 Ω to 299.9 kΩ
  • R~ resolution: 0.001 Ω to 100 Ω
  • R~ accuracy: ±(2% of rdg + 2 digit)
  • R~: Operating error ±(5% of rdg + 5 digit)
  • R~ measuring time: Typical 6 seconds
  • R~ max. interference voltage: 24 V, higher voltages measurement will not be started
  • R~ max overload: U rms max. = 250 V
  • R DC method:
    • Current-voltage measurement as per IEC61557-4 possible
    • 20 V DC
    • Short circuit current 250 mA DC
  • R DC 4-pole wires: H, S, ES can be extended without additional error
  • R DC wire E: Above 1 Ω can add 5 mΩ/Ω error
  • R DC range: 0.020 Ω to 300 kΩ
  • R DC: Display range 0.001 Ω to 299.9 kΩ
  • R DC resolution: 0.001 Ω to 100 Ω
  • R DC accuracy: ±(2% of rdg + 2 digit)
  • R DC: Operating error ±(5% of rdg + 5 digit)
  • R DC measuring sequence: Approx. 2 measurements/s
  • R DC measuring time: Typical 4 s including reversal of polarity (2-pole or 4-pole)
  • R DC max. interference voltage:
    • ≤ 3 V AC or DC
    • higher voltages measurement will not be started
  • Maximum inductivity: 2 Henry
  • R DC max. overload: U rms = 250 V
  • Lead compensation:
    • Available in RE 3-pole
    • RE 4-pole (clamp)
    • R AC and R DC 2-pole
  • Compensated value: R display = R measured - R compensated
  • RK setpoint:
    • Default 0.000 Ω
    • variable from 0.000 Ω to 29.99 Ω
  • Stakeless switch position: RA 4-pole (two clamp stakeless)
  • Stakeless loop resolution: 0.001 Ω to 0.1 Ω
  • Stakeless loop range: 0.02 Ω to 199.9 Ω
  • Stakeless loop accuracy: ±(7% rdg + 3 digit)
  • Stakeless loop: Operating error ±(10% rdg + 5 digit)
  • Stakeless measuring voltage:
    • Vm = 48 V AC (primary)
    • 128 Hz
  • Noise current IEXT:
    • Max 10 A AC (RA below 20 Ω)
    • max 2 A AC (RA above 20 Ω)
  • Stakeless principle:
    • Closed-loop resistance using two current transformers
    • automatic range selection
  • Stakeless conditions: Valid only with recommended current clamps at minimum distance specified
  • Dimensions (W x H x D): 250 x 133 x 187 mm
  • Weight:
    • ≤ 1.1 kg without accessories
    • 7.6 kg incl. accessories and batteries in carrying case
Optional Accessories
SKU Image Product name & short description
FLUKE ES-162P3-2 Fluke ES-162P3-2 3-Pole Stake Kit
Fluke ES-162P3-2 3-Pole Stake Kit
Needed to perform 3-Pole Fall-of-Potential testing (Stake testing).
FLUKE EI-1623 Fluke EI-1623 Selective/Stakeless Clamp Set
Fluke EI-1623 Selective/Stakeless Clamp Set
The Selective/Stakeless clamp set is used along with the Fluke 1623-2 and 1625-2 to perform Selective and Stakeless testing.
FLUKE EI-162BN Fluke EI-162BN 320 mm Diameter Split Core Transformer
Fluke EI-162BN 320 mm Diameter Split Core Transformer
Used as a Selective clamp for ground loop resistance measurement around power pylons.
FLUKE ES-162P4-2 Fluke ES-162P4-2 4-Pole Stake Kit
Fluke ES-162P4-2 4-Pole Stake Kit
Seven-piece set for performing 3- and 4-pole fall-of-potential testing that measures the ability of the earth ground system or individual electrode to dissipate energy from the site.
FLUKE CABLE-REEL-25M-BL Fluke Cable Reel 25M BL
Fluke Cable Reel 25M BL
Fluke Cable Reel 25M BL, ground/earth cable reel 25 m (81.25 ft), Part# 4343731, for Fluke 1623-2 and 1625-2.
FLUKE CABLE-REEL-25M-GR Fluke Cable Reel 25M GR
Fluke Cable Reel 25M GR
Fluke Cable Reel 25M GR, ground/earth cable reel 25 m (81.25 ft), Part# 4343746, for Fluke 1623-2 and 1625-2.
FLUKE CABLE-REEL-50M-RD Fluke Cable Reel 50M RD
Fluke Cable Reel 50M RD
Fluke Cable Reel 50M RD, ground/earth cable reel 50 m (162.5 ft), Part# 4343754, for Fluke 1623-2 and 1625-2.

Product reviews

Based on 0 reviews
0.0
Overall
5★ 0
4★ 0
3★ 0
2★ 0
1★ 0

Be the first to review “Fluke 1625-2 GEO Earth Ground Tester”

🎁 Write a review to earn 20 reward points — photo +10, video +15.
Accumulate reward points to redeem unique gifts from Minh Khang Vinatools. Log in
Please log in to submit a review.
Recently viewed
No items yet