Fluke electrical testers

Fluke 1663 Installation Multifunction Tester

★ 0.0 (0 reviews)
Sold: 0
Views: 0

Tests continuity at L-N, N-PE inputs. Tests smooth dc sensitive RCDs (Type B). Tests earth resistance, voltage, and frequency. Offers multiple test voltages: 50 V, 100 V, 250 V, 500 V, 1000 V. 6 mA RDC-DD testing for EV charging stations.

SKU: FLUKE 1663
Stock status: Out of stock
Contact us for pricing and availability.
Description

Key features

  • Tests continuity at L-N, N-PE inputs
  • Tests smooth dc sensitive RCDs (Type B)
  • Tests earth resistance, voltage, and frequency
  • Offers multiple test voltages: 50 V, 100 V, 250 V, 500 V, 1000 V
  • 6 mA RDC-DD testing for EV charging stations

Fluke 1663 Multifunction Installation Tester is the ideal choice for hard working professionals

The 1663 installation tester delivers the full-featured functionality and advanced measurement capabilities that professional installers need. It is compact and lightweight (less than 1.3 kg) and comes with a padded carrying and waist strap for convenient handling. Operation is intuitive and easily mastered by all levels of workers so you can put it to work immediately for quick and efficient testing to all local regulations. Additional features like On/Off switchable auto-start for RCD and loop test, as well as a self-test, saves time and gives you more confidence in your results.

Test EV charging station RCD type A-EV or RDC-DD DC protection devices

Perform tests on EV charging station DC protection devices using the RCD type B (smooth DC currents) VAR mode, which generates the test currents for RCD type A-EV or RDC-DD acc. to IEC 62955 (6/60/200 mA and ramp <2 to 6 mA ramp). This allows the quick an easy testing of additional 6 mA DC monitors on charging points and can be used in conjunction with the Fluke FEV100 or FEV300.

Software compatible

The Fluke 1663 is compatible with TruTest™, a Fluke software designed to eliminate the hassle associated with traditional electrical system data management and reporting. Whether you are testing fixed wire installations, or appliances in an office, verifying repairs in a workshop, or performing annual inspections, proper data management is critical for producing easy-to-understand reports for clients. TruTest™ Software allows you to quickly and easily import measurement results directly from your test instruments, manage files transferred from instruments, or manually enter data as needed.

Other useful capabilities:

  • Checks wiring polarity to detect broken N wires
  • Measures insulation resistance and loop and line resistance
  • Includes Z-max memory for loop tests to support easy evaluation of the highest loop test value
  • Provides unique zero adapter for fast, reliable and accurate test lead and mains cord compensation
  • Measures motor windings with continuity test
  • Calculates prospective earth fault current (PEFC/IK) and prospective short-circuit current (PSC/IK)
  • Measures RCD switching time and tripping level (ramp test)
  • Measures trip time and current for RCD type A & AC in one test
  • Measures RCD variable current
  • Provides automatic RCD test sequence
  • Includes a phase sequence indicator
  • Safety rated CAT III 500V, CAT IV 300V

What's in the box

  • 6x AA (IEC LR6) cell batteries
  • C1600 hard carrying case
  • Zero adapter
  • Heavy duty mains cord
  • STD standard test lead set
  • Padded carrying and waist strap
  • Quick reference guide
  • TP165X remote control probe and lead

Manuals + resources


Specifications

  • AC voltage range: 500 V
  • AC voltage resolution: 0.1 V
  • AC voltage accuracy: 0.8% + 3 (45 Hz to 66 Hz)
  • Input impedance: 360 kΩ
  • Overload protection: 660 V rms
  • Continuity range: 20 Ω to 2000 Ω (autoranging)
  • Continuity resolution: 0.01 Ω / 0.1 Ω / 1 Ω
  • Open circuit voltage: Above 4 V
  • Test voltages: 50-100-250-500-1000 V
  • Accuracy of test voltage: +10%, -0% at rated test current
  • Test voltage 50 V: Insulation ranges 20 MΩ / 50 MΩ
  • Test voltage 50 V resolution: 0.01 MΩ / 0.1 MΩ
  • Test voltage 50 V: Test current 1 mA @ 50 kΩ
  • Test voltage 100 V: Insulation ranges 20 MΩ / 100 MΩ
  • Test voltage 100 V resolution: 0.01 MΩ / 0.1 MΩ
  • Test voltage 100 V: Test current 1 mA @ 100 kΩ
  • Test voltage 250 V: Insulation ranges 20 MΩ / 200 MΩ
  • Test voltage 250 V resolution: 0.01 MΩ / 0.1 MΩ
  • Test voltage 250 V: Test current 1 mA @ 250 kΩ
  • Test voltage 500 V: Insulation ranges 20 MΩ / 200 MΩ / 500 MΩ
  • Test voltage 500 V resolution: 0.01 MΩ / 0.1 MΩ / 1 MΩ
  • Test voltage 500 V: Test current 1 mA @ 500 kΩ
  • Test voltage 1000 V: Insulation ranges 20 MΩ / 200 MΩ / 1000 MΩ
  • Test voltage 1000 V resolution: 0.01 MΩ / 0.1 MΩ / 1 MΩ
  • Test voltage 1000 V: Test current 1 mA @ 1 MΩ
  • Loop impedance range: 10 Ω (Hi current mΩ), 20 Ω, 200 Ω, 2000 Ω
  • Loop impedance resolution: 0.001 Ω / 0.01 Ω / 0.1 Ω / 1 Ω
  • PEFC, PSC range: 1000 A / 10 kA (50 kA)
  • PEFC, PSC resolution: 1 A / 0.1 kA
  • Computation:
    • PEFC = mains voltage / loop (L-PE) resistance
    • PSC = mains voltage / line (L-N) resistance
  • RCD type, model 1663: A, AC, G, S
  • RCD type notes:
    • AC responds to AC
    • G general, no delay
    • S time delay
    • A responds to pulsed signal
    • B responds to smooth DC signal
  • Current settings, x½ and x1: 10-30-100-300-500-1000 mA, VAR
  • Current settings, x5: 10-30-100 mA
  • VAR mode type B: 6, 60, 200 mA
  • Measurement range, RCD type G:
    • 310 ms (x½, x1)
    • 50 ms (x5)
  • Measurement range, RCD type S:
    • 510 ms (x½, x1)
    • 160 ms (x5)
  • EV / RDC-DD:
    • 6 mA - 10 s
    • 60 mA - 0.3 s
    • 200 mA - 0.1 s
  • Current setting notes:
    • 1000 mA type AC only
    • 700 mA maximum type A in VAR mode
  • VAR mode type B: Test currents per IEC 62955 for RCD A-EV, RDC-DD
  • VAR mode type B ramp: Below 2 mA to 6 mA
  • Current range: 30% to 110% of RCD rated current
  • Step size:
    • 10% of IΔN
    • 5% for type B
  • Ramp rise: Linear rising within 30 s
  • Dwell time:
    • Type G 300 ms/step
    • type S 500 ms/step
  • Measurement accuracy: ±5%
  • Specified trip current ranges (EN 61008-1)
  • Type AC: 50% to 100%
  • Type A above 10 mA: 35% to 140%
  • Type A ≤10 mA: 35% to 200%
  • Type B: 50% to 200%
  • Ramp current range notes:
    • 30% to 150% for Type A IΔN > 10 mA
    • 30% to 210% for Type A IΔN = 10 mA
    • 20% to 210% for Type B
  • Earth resistance range: 200 Ω to 2000 Ω
  • Earth resistance resolution: 0.1 Ω / 1 Ω
  • Earth resistance frequency: 128 Hz
  • Output voltage: 25 V
  • Phase sequence indication: Phase sequence indicator icon is active
  • Battery size, quantity: Type AA, 6 ea.
  • Sealing: IP40
  • Safety: Complies with EN/IEC 61010-1 and EN/IEC 61010-2-034
  • Overvoltage:
    • CAT III 500 V
    • CAT IV 300 V
  • Performance: EN61557-1 to EN61557-7 and EN61557-10
  • Size (L x W x H): 10 x 25 x 12.5 cm
  • Weight: 1.3 kg incl. batteries

Product reviews

Based on 0 reviews
0.0
Overall
5★ 0
4★ 0
3★ 0
2★ 0
1★ 0

Be the first to review “Fluke 1663 Installation Multifunction Tester”

🎁 Write a review to earn 20 reward points — photo +10, video +15.
Accumulate reward points to redeem unique gifts from Minh Khang Vinatools. Log in
Please log in to submit a review.
Recently viewed
No items yet